THRP 300V

VERTICAL RECOVERY DEHUMIDIFIERS


The vertical THRP-300 V dehumidifier with recuperator has been designed to be mounted on walls. Careful attention has been paid to designing the units in order to achieve high manufacturing and operational

standards and to maximize its strength and provide complete versatility and performance adaptation in order to reach a high degree of overall efficiency.

The unit is fitted with two brushless DC fans with automatic electronic flow management that can be regulated from a highly intuitive remote display. Flow control is continuous and the flow rate is maintained at the set level even when there is a natural increase in the pressure drop in the filters during operation. The use of two centrifugal fans ensures silent operation, up to three times less noise than with PlugFan fans.

Particular attention has been paid to the dehumidifying and condensation collection section. A special paint is used so that drops of moisture run off directly into the collection tank that is made entirely of STAINLESS steel. This solution eliminates problems associated with the formation of mould and bacteria by preventing water stagnation in humid zones.

The THRP-300 V makes it possible to achieve a renewal efficiency of over 90%. The unit is fitted with pre- and post- cooling coils as standard, guaranteeing optimum performance and temperature control of the treated air.

They work in five ways:

  • Dehumidification
  • Ventilation
  • Integration
  • Renewal
  • Freecooling
[lvca_tabs style="style4" highlight_color="#e06223" mobile_width="600"][lvca_tab tab_title="Data Sheet"]

MODEL U.M. DRP300AE
Condensate humidity (26° - 65%) l/day 36
Nominal air flow rate m3/h 300
Input power W 480
Cooling capacity W 920
Cooling capacity (H2O =7°) W 1150
Supply V/Ph/Hz 230/1/50
Maximum electrical input power W 590
Chiller unit maximum power input (integration) W 1400
Chiller unit maximum power input (H2O= 7°) W 1760
Water flow rate (15°C) l/h 360
Water flow rate (15°C) (neutral dehumidification) l/h 105
Water flow rate (7°C) (integration) l/h 360
Load loss kPa 17
Treated airflow m3/h 150400
Maximum head (300m3/h) Pa 400
Air flow rate extraciton/renewl m3/h 100300
Maximum head (250m3/h) Pa 300
Nominal efficiency (350 m3/h) % 88
Maximum efficiency (100 m3/h) % 93
Refrigerant (R134a) gr 110
Sound power level dB(A) 44
Sound pressure level dB(A) 36
Weight kg 58
Outer machine dimensions
Height mm 1380
Width mm 700
Depth mm 354

Performance according to room temperature, relative humidity and chilled water temperature.

Room temperature: 26° C
Litres/ Day Relative humidity
55% 65%
18 23,1 27,9
T water 15 28,9 35,6
12 34,3 42,5
Temperatura ambiente: 24° C
Litres/ Day Relative humidity
55% 65%

Maximum recycled sensible heat output in winter (air flow rate 300 m3/h) according to the room temperature of the water in the system (water flow rate 600l/h)

RP300
Recirculation sensible heat [kW ] Room temperature
20 22 24 28
T water 35 1,8 1,6 1,4 0,9
40 2,5 2,2 2,0 1,6
45 3,1 2,9 2,6 2,1
50 3,6 3,5 3,3 2,7
55 4,3 4,0 3,9 3,4

[/lvca_tab][lvca_tab tab_title="Features"]

SPECIFICATION

Casing
The THRP-300 V is made of pre-painted hot-dip galvanized sheet metal that ensures a high resistance to corrosion. The structure is self-supporting with removable panels to make inspection and maintenance easier. The stainless steel collection tank is placed at a steep angle towards the drainage channel to prevent water stagnation and consequent mould formation.

Cooling circuit
The cooling circuit it is made up of components supplied by leading international companies and the cooling circuit is assembled entirely in Italy. It is made according to the mandatory technical standards regarding braze-welding processes. The refrigerant gas used is R134A.

Compressor
Reciprocating compressor with thermal cut-out. It is mounted on special anti-vibration mounts to reduce noise. Condensers, evaporators and post treatment coils pressure drop and therefore allows the speed of the fans to be reduced (resulting in reduced machine noise).

Condensers, evaporators and post treament coils
The condensing and evaporating coils are made of 5/16" grooved copper tubes and alluminium fins with a special hydrophilic paint that encorages water run-off and maximises efficiency. The geometry of these heat exchangers allows a low air-side pressure drop and therefore allows the speed of the fans to be reduced (resulting in reduced machine noise). The pre- and post-treatment coils guarantee that the air temperature is kept constant in all conditions.

Fan
The unit is fitted with two brushless DC fans with automatic electronic flow management

Air filter
Class G4 supplied with the unit.

Controller
The unit is equipped with a sophisticated microcontroller that controls all the machine operating parameters according to
external requests. The unit is supplied with a series of sensors and actuators that allow the control unit to control the system
and any faults that may arise.

Electrical panel
The electrical panel is designed to comply with the mandatory European safety regulations. The electrical panel can be accessed
by opening the special access panel. There are several inputs on the terminal board that are used for operating the
unit in the various modes of operation.

Testing
All units are fully assembled and wired at the factory, they undergro a leak test, vacuum cycle, and are filled with an eco-friendly refrigerant. They undergo a complete functional test before being shipped. All units comply with European Directives and have a CE marking and relative certificated of conformity[/lvca_tab][lvca_tab tab_title="Quote"]

Contact us for a quote






[/lvca_tab][/lvca_tabs]