THS-D 250

DEHUMIDIFIERS


The THS-D250 dehumidifier has been designed to be installed in suspended ceilings.

It has an enlarged fan\ to overcome the problem of complex ducting and to reduce the amount of noise with an equivalent air flow.

The filtering section is encased in the machine and the accessibility for removing the filter is possible on the four sides depending on the application of the dehumidifier.

These work in two ways: dehumidification and ventilation.

In the version where the two functioning methods are integrated, the possibility of humidifying and cooling the air are added.

 

MODEL THS-D250 STANDARD INTEGRATION
Condensate humidity (26°-65%) l/day 24 26
Input power W 29 260
Cooling capacity W - 620
Supply V/Ph/Hz 230/1/50 230/1/50
Maximum power input W 340 340
Water flow rate (15°C) l/h 240 240
Refrigerator Input power W 830 1110
Load loss kPa 5 5
Air flow rate m3/h 250 250
Maximum head (Speed.3) Pa 60 60
Medium head (Speed.2) Pa 40 40
Minimum head (Speed.1) Pa 10 10
Refrigerant (R134a) gr 200 120
Sound power level dB(A) 41 41
Sound pressure level dB(A) 33 33
Outer machine dimensions
Height mm 249 249
Width mm 525 525
Depth mm 650 650

PERFORMANCE ACCORDING TO ROOM TEMPERATURE, RELATIVE HUMIDITY AND CHILLED WATER TEMPERATURE

STANDARD
Room temperature: 26° C
Litres / Day Relative humidity
55% 65%
T water 18 15,6 18,8
15 19,5 23,9
12 23,1 28,6
Room temperature: 24° C
Litres / Day Relative humidity
55% 65%
T water 18 9,8 11,9
15 12,3 15,10
12 14,60 18,10

 

INTEGRATION
Room temperature: 26° C
Litres / Day Relative humidity
55% 65%
T water 18 17,10 20,10
15 21,4 26,3
12 25,4 31,5
Room temperature: 24° C
Litres / Day Relative humidity
55% 65%
T water 18 10,8 13,10
15 13,5 16,60
12 16,00 19,90

Contact us for a quote






© 2017 Thermics Energie